Technical connection conditions for EGS and storage

When implementing an EGS, please note our TCC for EGS. These also apply for storage units.

Technical connection conditions (TCC) for the parallel operation of energy generation systems (EGS) and storage units in the Primeo Energie power supply network

Diagrams:

Factory acceptance and standards to be set

Primeo Energie carries out a factory acceptance test at all EGS sites. The producer confirms to Primeo Energie that all specifications have been complied with and that the settings are in line with the TCC for EGS.

As a rule, and unless otherwise stated on the application for connection, the current country setting for Switzerland must be set in accordance with NA/EGS-CH. Alternatively, the current VDE-AR-N 4105:2018—11 data record (or for medium voltage 4110) can be selected in exceptional cases. Older country rates which are no longer valid may no longer be used.

For EGS > 3.6 kVA with Type 2 converter, characteristic curve Q(U) must be set in accordance with Appendix D of TCC for EGS (static grid support). With an output ≤ 3.6 kVA, cosφ = 1 can be used.